Table Size of Cable and Breaker Compressor
Cable has a very important role in its function as a conductor. We must be selective in choosing and using a cable that suits your needs. Especially for large power tools with more than ten Kilo Watt (KW) such as compressors.
Below I give a table size of cable and breaker compressor
Note: Maximum cable length is 50 m, if more than that use a larger cable
N: Neutral
E: Earth
Reference: Operator's Manual, Ekomak Compressor
Below I give a table size of cable and breaker compressor
No. | KW | HP | CABLE SIZE | CIRCUIT BREAKER |
1 | 15 | 20 | 3 X 6 mm2 + N + E | 40 A |
2 | 18 | 25 | 3 X 10 mm2 + N + E | 40 A |
3 | 22 | 30 | 3 X 10 mm2 + N + E | 50 A |
4 | 30 | 40 | 3 X 16 mm2 + N + E | 63 A |
5 | 37 | 50 | 3 X 25 mm2 + N + E | 80 A |
6 | 45 | 60 | 3 X 25 mm2 + N + E | 100 A |
7 | 55 | 75 | 3 X 35 mm2 + N + E | 125 A |
8 | 75 | 100 | 3 X 50 mm2 + N + E | 160 A |
9 | 90 | 125 | 3 X 70 mm2 + N + E | 200 A |
10 | 110 | 150 | 3 X 95 mm2 + N + E | 250 A |
11 | 132 | 180 | 3 X 120 mm2 + N + E | 250 A |
12 | 160 | 220 | 3 X 120 mm2 + N + E | 300 A |
13 | 200 | 270 | 3 X 150 mm2 + N + E | 400 A |
14 | 250 | 340 | 3 X 150 mm2 + N + E | 500 A |
Note: Maximum cable length is 50 m, if more than that use a larger cable
N: Neutral
E: Earth
Reference: Operator's Manual, Ekomak Compressor